PNGRB CGD Amendment Regulations 2026: New PNG Pipeline, MLC Pipe and Safety Requirements
Quick note
Below is the official summary and the reference document preview. Use “Open PDF” for full screen view.
Schedule a Call Back
Summary
The Petroleum and Natural Gas Regulatory Board has changed some of the technical and safety rules that apply to City Gas Distribution networks in India.
The new rules were issued through the Petroleum and Natural Gas Regulatory Board (Technical Standards and Specifications including Safety Standards for City or Local Natural Gas Distribution Networks) Amendment Regulations, 2026, dated 18 September 2026.
The amendment does not rewrite the entire CGD framework. Instead, it changes selected provisions dealing with pipe materials, PNG service-line installations, use of Multi-Layered Composite pipes, pressure-regulating stations, existing LPG manifold pipelines and maintenance of thermoplastic pipes.
For CGD companies, contractors and engineering teams, the main task now is to identify which existing specifications, drawings, SOPs and field practices are affected by the revised wording.
The amendment is issued under the PNGRB Act, 2006 and further amends the 2008 CGD technical and safety regulations. It comes into force from the date of publication in the Official Gazette. 276594
PNGRB Amendment Regulations 2026 at a Glance
| Particular | Details |
| Issuing Authority | Petroleum and Natural Gas Regulatory Board |
| Regulator | PNGRB |
| Notification Date | 18 September 2026 |
| File Number | PNGRB/Tech/1-T4SCGD/(4)/2023-Part(1) (E-6228) |
| Governing Law | Petroleum and Natural Gas Regulatory Board Act, 2006 |
| Principal Regulations | PNGRB Technical Standards and Specifications including Safety Standards for City or Local Natural Gas Distribution Networks Regulations, 2008 |
| Sector | City Gas Distribution |
| Main Area | PNG technical and safety standards |
| Schedules Amended | Schedule 1A, Schedule 1D and Schedule 1E |
| Effective Date | Date of publication in the Official Gazette |
| Separate Transition Period | Not expressly specified |
| New Licence Requirement | Not introduced by this amendment |
| New Fee Schedule | Not prescribed |
| Main Technical Changes | GI pipe use, copper tubing, MLC pipes, PE pipe restriction, DPRS/IPRS spacing, LPG-to-PNG pipeline use, squeeze-off rules |
Regulatory Framework Behind the PNGRB CGD Technical Standards
A mix of authorisation conditions, technical standards, safety requirements and operating rules governs City Gas Distribution networks.
The technical framework relevant here comes from the PNGRB (Technical Standards and Specifications including Safety Standards for City or Local Natural Gas Distribution Networks) Regulations, 2008.
These regulations deal with the way CGD infrastructure is designed, installed, operated, and maintained.
The 2026 amendment changes three specific schedules.
Schedule 1A- Materials and Equipment
This schedule deals with materials used in the network and associated equipment.
The 2026 amendment changes the position relating to:
- GI pipes
- copper pipes and tubing
- MLC pipes
- PE pipes
- meter-to-appliance connections
- reinforced rubber hose
Schedule 1D- Design, Installation and Testing
This part covers engineering and installation-related matters.
The amendment changes:
- DPRS/IPRS separation wording
- steel-pipe design table
- customer meter/regulator heading
- use of existing LPG manifold pipelines for PNG supply
Schedule 1E- Distribution Piping Maintenance
This section now contains revised requirements on squeezing and reopening thermoplastic pipes.
These are targeted amendments. They do not replace the full 2008 technical framework.
Who Is Affected by the PNGRB Amendment Regulations 2026?
The biggest impact will be on organisations directly involved in CGD design, installation, operation and maintenance.
City Gas Distribution entities
CGD entities may need to examine whether their existing technical specifications still match the amended regulations.
Areas requiring attention may include:
- material specifications
- standard drawings
- service-line design
- meter connections
- DPRS/IPRS layouts
- maintenance SOPs
- LPG-to-PNG conversion projects
Engineering and project teams
Design engineers need to pay particular attention to:
- pipe material
- location of copper tubing
- MLC installation conditions
- DPRS/IPRS separation
- existing LPG manifold networks
Installation contractors
Field teams may need revised work instructions where older specifications are still being used.
Operations and maintenance teams
The squeeze-off changes directly affect maintenance practice.
Housing societies and residential complexes
This amendment is especially relevant where an existing reticulated LPG manifold pipeline is proposed to be used for PNG supply.
Material suppliers
Suppliers of GI pipes, copper tubing, MLC pipes and reinforced hoses may face more specific technical requirements in project specifications.
What Has Changed Under the PNGRB Amendment Regulations 2026?
The amendment touches several small but technically important areas.
The main changes are:
- clearer use of GI pipes in above-ground service lines
- location-based restrictions on copper tubing
- recognition of MLC piping under prescribed standards
- controlled use of MLC outside the kitchen and upstream of the consumer meter
- restrictions on above-ground PE piping
- specific meter-to-appliance connection options
- revised 2-metre DPRS/IPRS separation wording
- removal of the “pipelines on bridges” row from Table 2
- express provision for using existing LPG manifold pipelines for PNG supply
- marking and spacing requirements for thermoplastic pipe squeeze-off locations
The detailed amendments appear in Schedules 1A, 1D and 1E. 276594
Schedule-Wise Changes Under the 2026 Amendment
| Schedule | Area | Main Change |
| Schedule 1A | Materials and Equipment | Pipe material, MLC, copper, PE, and appliance-connection requirements. |
| Schedule 1D | Design, Installation and Testing | DPRS/IPRS separation, bridge pipeline entry, meter heading and LPG manifold reuse. |
| Schedule 1E | Distribution Piping Maintenance | Squeeze-off marking and minimum spacing. |
New Requirements for PNG Service Line Pipes and Tubing
GI Pipes in Above-Ground Service Lines
The amended provision says that Galvanized Iron pipes shall be used in above-ground service lines up to the consumer meter or meter control valve.
This gives project teams a clearer reference point for material selection.
The same provision also requires GI pipes and copper tubing to conform to the requirements given in Annexure IV of the standard.
Use of non-galvanised pipes is to be restricted as far as possible. Where they are used, they must be properly protected and painted. 276594
What this means in practice
Engineering and procurement teams should not look only at pipe diameter or pressure rating.
They also need to check:
- type of pipe
- location of installation
- position in relation to the consumer meter
- applicable Annexure IV requirements
- corrosion protection where relevant
Copper Pipe and Tubing Requirements
Copper continues to be recognised, but the amended rule makes its location much more important.
For above-ground service lines, copper tubing after the consumer meter may be used in a manner that keeps it away from third-party access.
Before the consumer meter, copper pipe or tube should be used inside the kitchen only.
This is one of the most important details in the amendment because it prevents a broad reading that copper can be used anywhere upstream of the meter.
Why location matters
The amendment treats pipe use differently depending on whether it is:
- upstream of the consumer meter
- downstream of the consumer meter
- inside the kitchen
- outside the kitchen
That means the same material may not be acceptable in every location.
For field teams, installation drawings should clearly show this distinction.
PNGRB Requirements for Multi-Layered Composite Pipes in PNG Service Lines
Multi-Layered Composite pipes receive much clearer treatment under the 2026 amendment.
An MLC pipe can be used as an alternative to copper pipe or tube in the situations covered by the regulation, provided it meets the prescribed technical standard.
The amendment recognises MLC pipe conforming to:
- ISO 17484-1
- IS 17544
Where compliant MLC pipe is used upstream of the consumer meter and outside the kitchen, additional requirements apply.
In such cases, the relevant PNGRB Guidelines for Controlled Utilization of Multi-Layered Composite Piping Systems for above-ground PNG service lines must be followed.
These guidelines are linked with:
- safe installation
- prescribed installation methods
- protection of the pipe
- protection against third-party damage
Material compliance is only one part of the requirement
A pipe meeting ISO 17484-1 or IS 17544 is not automatically suitable for every location.
The installation conditions must also be checked.
A project team should therefore look at:
- whether the MLC pipe meets the prescribed standard
- where the pipe is being installed
- whether it is upstream or downstream of the meter
- whether it is inside or outside the kitchen
- whether the applicable PNGRB MLC guidelines apply
Can PE Pipes Be Used for Above-Ground PNG Service Lines?
The amended provision states that Polyethylene pipe shall not be used for above-ground gas pipes unless specifically permitted in the regulations. 276594
This should not be interpreted to mean that PE pipe is banned from the entire City Gas Distribution network.
The restriction here is specifically about above-ground gas piping.
Any underground application or other use must be assessed under the relevant part of the regulations.
What Pipes or Hoses Can Be Used Between the Consumer Meter and Gas Appliance?
The amendment also covers the short connection between the consumer meter set assembly and the consumer's gas appliance.
The permitted options mentioned are:
- Galvanized Iron pipe
- Copper tubing meeting Annexure IV requirements
- steel-reinforced rubber hose
Where steel-reinforced rubber hose is used, it must conform to IS 9573 Part 2. 276594
What contractors should check
Before completing a consumer-side connection, the installer should check:
- type of connection being used
- compliance of copper tubing with Annexure IV, where relevant
- compliance of reinforced rubber hose with IS 9573 Part 2
- suitability of the connection for the approved installation
Technical Standards Referred to in the Amendment
| Standard / Reference | Related Area | Relevance |
| ISO 17484-1 | MLC pipe | Technical conformity |
| IS 17544 | MLC pipe | Technical conformity |
| Annexure IV | GI pipe and copper tubing | Material requirements |
| IS 9573 Part 2 | Steel-reinforced rubber hose | Meter-to-appliance connection |
| PNGRB MLC Guidelines | MLC piping outside kitchen/upstream of meter | Installation and protection |
| PNGRB LPG-to-PNG Guidelines | Existing LPG manifold system | Safety and pipeline integrity |
Reference to an IS standard should not automatically be treated as a new BIS registration requirement. The amendment itself does not create a separate BIS registration process for these materials.
Revised Safety Requirements for DPRS and IPRS Installations
The amendment also changes the wording around above-ground pressure-regulating stations.
A Distribution Pressure Regulating Station (DPRS) and an Individual Pressure Regulating Station (IPRS) are used to regulate gas pressure before it moves further through the distribution system.
For above-ground DPRS/IPRS installations:
- security fencing is required according to local authority requirements
- the distance between the DPRS/IPRS enclosure and the permanent wall of the nearest building or structure must not be less than 2 metres
What has actually changed?
Earlier wording referred to the distance between the fencing and the wall of the nearest building or structure.
The revised text specifically refers to the DPRS/IPRS enclosure and the permanent wall of the nearest building or structure.
That wording should be reflected correctly in technical drawings and layout reviews.
What Has Changed for Pipelines on Bridges?
Under the heading dealing with steel pipes, the fourth row of Table 2 – Design Factors for Steel Pipe Construction, relating to “Pipelines on bridges,” has been omitted. 276594
The notification does not say that pipelines on bridges are now prohibited.
It also does not explain within this amendment what alternative design factor should automatically apply.
For that reason, engineers should read the amended provision together with the principal regulations and any other applicable PNGRB technical requirements before making a design decision.
Change in Customer Meter and Regulator Installation Wording
One of the smaller amendments is a change in the heading dealing with customer meters and regulators.
The earlier wording:
Location for Customers' and Regulator Installations
is replaced by:
Location for Customers' Meter and Regulator Installations
This appears to be mainly a wording correction. The notification does not attach a separate technical condition to this particular heading change.
Can Existing LPG Manifold Pipelines Be Used for PNG Supply?
Yes, but the amendment does not provide unrestricted permission.
It specifically deals with existing:
- carbon steel pipelines
- mild steel pipelines
- reticulated LPG manifold pipeline systems
used in:
- housing societies
- residential complexes
Where such an existing LPG manifold pipeline is proposed to be used for PNG supply, the relevant PNGRB guidelines must be followed to ensure the safety and integrity of the pipeline system. 276594
This does not mean every LPG system can automatically be converted
An existing LPG manifold system may have been designed and operated under different conditions.
Before it is used for PNG, its suitability has to be considered within the framework referred to by PNGRB.
The amendment therefore creates a regulated route for the use of existing infrastructure rather than a blanket approval.
What Housing Societies Should Check Before LPG-to-PNG Conversion
Housing societies considering a shift from an existing reticulated LPG arrangement to PNG should first coordinate with the authorised CGD entity.
Requirement expressly referred to in the amendment
The applicable PNGRB guideline for use of existing LPG manifold pipelines for PNG supply must be followed.
Practical checks that may be required
Depending on the installation, the technical team may need to review:
- pipeline material
- age and condition
- visible corrosion
- pipe routing
- joints and fittings
- valves
- previous maintenance records
- available drawings
- pressure suitability
- accessibility
- integrity of the overall system
These checks are practical implementation considerations. The amendment itself does not set out this exact checklist.
New Squeeze-Off and Reopening Rules for Thermoplastic Pipes
A squeeze-off is a maintenance method used to temporarily stop or control gas flow in certain thermoplastic pipes by compressing the pipe.
The 2026 amendment introduces clearer restrictions on what happens after such a location has been reopened.
Three rules stand out:
- The place where squeezing and reopening has already been carried out must be properly marked.
- The reopened pipe cannot be squeezed again at the same location.
- There must be at least 1 metre between consecutive squeeze-off locations.
Why the marking requirement matters
A maintenance crew may return to the same pipeline after months or years.
If the earlier squeeze-off point is not identified, the same section of pipe could be selected again.
The amended rule removes that ambiguity by requiring proper marking.
Key Technical Values Under the 2026 Amendment
| Requirement | Technical Value / Standard |
| DPRS/IPRS separation | Minimum 2 metres |
| Consecutive squeeze-off locations | Minimum 1 metre |
| MLC pipe | ISO 17484-1 or IS 17544 |
| Steel-reinforced rubber hose | IS 9573 Part 2 |
| GI and copper requirements | Annexure IV |
Material-Wise Requirements for PNG Service Lines
| Material | Where It Is Relevant | Technical Requirement | Main Limitation |
| GI pipe | Above-ground service line up to consumer meter/control valve | Annexure IV | Use according to prescribed application |
| Copper tubing | Before/after meter in specified situations | Annexure IV | Location-based restrictions |
| MLC pipe | Alternative to copper in permitted situations | ISO 17484-1 or IS 17544 | PNGRB guideline conditions where applicable |
| PE pipe | Above-ground gas piping | Only where specifically permitted | General above-ground use restricted |
| Steel-reinforced rubber hose | Meter-to-appliance connection | IS 9573 Part 2 | Must conform to prescribed standard |
Old vs New PNGRB CGD Technical Requirements
| Compliance Area | Earlier Position | 2026 Position | Business Meaning |
| GI pipe | Earlier provisions covered service piping | GI use up to consumer meter/control valve is expressly stated | Material specifications should be reviewed |
| Copper pipe | Earlier treatment was broader | Location before the meter is restricted | Drawings and installation practice matter |
| MLC pipe | Earlier position not fully reproduced in amendment | MLC recognised with specified standards and conditions | Additional design option with safeguards |
| DPRS/IPRS | Distance wording referred to fencing | New wording refers to enclosure and permanent wall | Layout measurement point is clearer |
| Pipeline on bridges | Specific table row existed | Row deleted | Engineering interpretation requires care |
| LPG manifold system | Earlier wording did not contain the new express provision | Existing CS/MS LPG manifold systems addressed for PNG use | Residential conversion projects need guideline-based review |
| Squeeze-off | Earlier entries replaced | Marking, no repeat squeeze at same point and 1 m distance specified | Maintenance SOPs need review |
When Do the PNGRB Amendment Regulations 2026 Come Into Force?
The regulations come into force on the date of publication in the Official Gazette. 276594
There is no separate future commencement date mentioned in the amendment text.
Is There a Transition Period?
The notification does not expressly provide a separate transition period.
Businesses should therefore avoid assuming that a general grace period of three months, six months, or any other duration is available.
If PNGRB later issues a separate clarification or implementation direction, that document would need to be considered independently.
Do Existing PNG Pipelines Need to Be Replaced?
The notification does not say that every existing PNG pipeline must be replaced.
That distinction is important.
A technical amendment may require a company to review an installation without automatically requiring physical replacement.
CGD entities should check:
- whether the existing installation falls within the amended provision
- whether the installation predates the amended wording
- whether separate PNGRB guidelines apply
- whether an engineering integrity review is required
- whether the project is existing, ongoing or new
A blanket replacement statement would go beyond what this notification says.
Does the Amendment Introduce a New Licence or Registration?
These technical amendments create no new licence or registration process.
The notification deals with technical standards, installation, material selection, and maintenance.
Any existing PNGRB authorisation requirement continues to be governed by the relevant legal framework separately.
Does the Amendment Introduce New Fees or Penalties?
The amendment itself does not prescribe a new fee schedule or a specific penalty amount for these changes.
Businesses should therefore not treat this notification as a new fee or penalty notification.
Any enforcement consequence would need to be examined under the applicable parent law, regulations or authorisation conditions.
Impact on City Gas Distribution Companies
Engineering and Design
Engineering teams are likely to carry the heaviest implementation responsibility.
Existing design documents may need to be checked for:
- service-line material
- copper pipe location
- MLC use
- DPRS/IPRS separation
- meter connection design
- LPG manifold conversion
Procurement
Procurement teams should ensure that technical purchase specifications match the amended requirements.
This may involve checking:
- Annexure IV requirements
- ISO 17484-1
- IS 17544
- IS 9573 Part 2
Construction and Installation
Contractors working from older drawings or specifications may need updated instructions.
This is particularly relevant where:
- copper is used upstream of a meter
- MLC pipe is installed outside a kitchen
- a DPRS/IPRS is being positioned
- an existing LPG pipeline is being reused
Maintenance
The squeeze-off amendment has a direct impact on field maintenance.
Teams should ensure that:
- previous squeeze locations are marked
- the same reopened point is not squeezed again
- one metre is maintained between consecutive squeeze-off locations
Existing Residential Networks
Residential projects with older LPG manifold systems deserve separate attention because the amendment now expressly recognises their possible use for PNG subject to PNGRB guidelines.
Impact on Housing Societies and Residential Complexes
Housing societies may benefit where existing LPG infrastructure can be safely retained for PNG use, but this should not be treated as a simple infrastructure reuse decision.
The authorised CGD entity may need to assess:
- condition of the existing pipeline
- material
- safety
- integrity
- suitability for PNG service
- compliance with the relevant PNGRB guideline
For societies, the practical benefit is that existing infrastructure may be considered rather than automatically discarded, provided the applicable technical requirements are met.
Impact on PNG Contractors and Installation Agencies
Contractors should pay close attention to site-specific requirements.
A drawing that was technically acceptable under an earlier specification may need to be rechecked if it involves:
- copper upstream of the meter
- MLC piping
- above-ground PE piping
- consumer-appliance hose
- DPRS/IPRS location
- existing LPG pipelines
Site supervisors should also make sure that older work instructions are not being used without review.
Impact on Pipe, Tubing and Gas Equipment Suppliers
Suppliers may see tighter technical specifications in tenders and procurement orders issued by CGD entities.
Products most directly affected include:
- GI pipes
- copper tubing
- MLC pipes
- steel-reinforced rubber hoses
Suppliers should be ready to provide technical data showing conformity with the relevant standard where required.
The notification, however, does not itself create a new standalone product registration process.
What CGD Operators Should Review in Existing Projects
Existing projects should not be ignored simply because construction has already started.
A structured review can cover:
Drawings
Check whether the pipeline route and material remain consistent with the amended position.
Approved material list
Confirm whether the selected pipe or hose still fits the application.
MLC installations
Check both material conformity and installation location.
Copper installations
Confirm whether copper use before the meter is within the permitted location.
DPRS/IPRS
Recheck enclosure-to-wall distance.
LPG manifold systems
Identify any residential project using an existing LPG pipeline for PNG.
Maintenance records
Make sure squeeze-off locations can be identified.
What Should Be Checked Before Starting New PNG Installations?
Before construction starts, project teams should verify:
- approved pipe material
- meter position
- copper pipe location
- MLC standard
- MLC installation safeguards
- PE pipe restriction
- meter-to-appliance connection
- DPRS/IPRS separation
- LPG-to-PNG conversion conditions
- maintenance-related design considerations
This early review can reduce the need for design changes after installation has already begun.
PNGRB 2026 Compliance Checklist for CGD Entities
| Review Area | What Should Be Checked | Nature |
| GI pipe | Use up to consumer meter/control valve | Regulatory requirement |
| Copper pipe | Location before and after meter | Regulatory requirement |
| MLC pipe | ISO 17484-1 or IS 17544 | Regulatory requirement |
| MLC installation | PNGRB guideline where applicable | Regulatory requirement |
| PE pipe | Above-ground restriction | Regulatory requirement |
| Meter connection | Permitted pipe/hose option | Regulatory requirement |
| Rubber hose | IS 9573 Part 2 | Regulatory requirement |
| DPRS/IPRS | Minimum 2 m distance | Regulatory requirement |
| LPG manifold reuse | Applicable PNGRB guideline | Regulatory requirement |
| Squeeze-off marking | Previous location identified | Regulatory requirement |
| Squeeze spacing | Minimum 1 m | Regulatory requirement |
| Drawings | Review against amendment | Recommended internal control |
| SOPs | Update where needed | Recommended internal control |
Technical and Operational Risks to Avoid
The amendment highlights several areas where an incorrect interpretation can create compliance problems.
Businesses should avoid:
- using the same pipe material across all locations without checking the rule
- assuming copper may be used anywhere upstream of the consumer meter
- selecting MLC pipe only on the basis of material certification
- ignoring MLC installation safeguards
- using PE pipe above ground without confirming that the regulations permit it
- measuring DPRS/IPRS spacing from the wrong reference point
- assuming an existing LPG pipeline is automatically suitable for PNG
- squeezing the same reopened thermoplastic pipe location again
- failing to mark a previous squeeze-off point
- ignoring the one-metre minimum distance
Potential Benefits of the 2026 Amendment
The amendment can make technical decisions easier where earlier wording left room for interpretation.
Possible benefits include:
Better material clarity
GI, copper, MLC and PE now have clearer location-based treatment.
More controlled MLC use
The rule recognises MLC but also ties it to technical standards and installation safeguards.
More precise DPRS/IPRS layout requirements
The revised wording gives a clearer reference point for the two-metre distance.
Safer maintenance practices
The squeeze-off provision reduces the risk of repeated work at the same point.
Better use of existing infrastructure
Housing societies may be able to use existing LPG manifold systems for PNG where safety and integrity conditions are met.
Implementation Challenges for CGD Operators
The main challenge is likely to be coordination across departments.
A technical amendment may look small on paper, but it can affect:
- drawings
- procurement
- contractor instructions
- material approvals
- site inspections
- maintenance manuals
- residential conversion plans
Large CGD companies may already have hundreds of approved drawings and standard specifications in circulation.
The practical task is therefore to identify exactly which ones need revision rather than changing every document unnecessarily.
Business and Regulatory Perspective
The 2026 amendment does not add a new layer of licensing.
Its focus is more technical.
PNGRB is tightening or clarifying how certain materials and installations should be handled across the CGD network.
For businesses, the bigger risk is not missing a new application form. It is continuing to use an old engineering specification after the technical rule has changed.
That is why engineering, procurement, compliance and field teams need to read the amendment together rather than treating it as a legal-team-only update.
What Businesses Should Do Next
A sensible review can be carried out in the following order:
1. Map the affected projects
Identify new, ongoing and existing projects involving the amended provisions.
2. Compare current specifications
Check current standard specifications against the revised Schedule 1A, 1D, and 1E requirements.
3. Review drawings
Focus on copper, MLC, DPRS/IPRS, and existing LPG manifold infrastructure.
4. Check procurement documents
Make sure material descriptions refer to the correct standards.
5. Review contractor SOPs
Remove outdated instructions where necessary.
6. Update maintenance practice
Include squeeze-off marking and one-metre spacing.
7. Maintain review records
Keep a record of the technical and regulatory review carried out.
8. Monitor related PNGRB guidelines
Some provisions, especially MLC and LPG-to-PNG use, depend on separate PNGRB guidelines referred to in the amendment.
How Corpseed Can Help with PNGRB and CGD Regulatory Compliance
The difficult part of a technical notification is often not reading the amendment itself. The challenge is understanding which part applies to a particular project, installation, or business activity.
Corpseed can support CGD companies, contractors and other affected businesses through regulatory compliance services such as:
- PNGRB applicability assessment
- CGD regulatory compliance review
- technical regulation mapping
- compliance gap assessment
- review of regulatory documents
- identification of applicable PNGRB requirements
- support in understanding referenced standards
- licence and approval advisory where separately required
- ongoing regulatory update support
- compliance documentation assistance
For businesses dealing with multiple technical standards, regulatory compliance services can help connect the legal requirement with the engineering and operational documents already being used internally.
Corpseed does not replace the role of competent engineers, statutory authorities, or technical inspection bodies. Its role is to support businesses in understanding the applicable regulatory framework and organising compliance requirements correctly.
Key Takeaways
The PNGRB CGD Amendment Regulations 2026 change selected technical and safety requirements under the existing City Gas Distribution framework.
The main points businesses should remember are:
- GI pipe use up to the consumer meter or meter control valve has been clarified.
- Copper use before the consumer meter is restricted to the kitchen in the stated provision.
- MLC pipe must meet ISO 17484-1 or IS 17544 and may also require compliance with PNGRB installation guidelines.
- PE pipe cannot be used for above-ground gas piping unless specifically permitted.
- Steel-reinforced rubber hose for meter-to-appliance connection must conform to IS 9573 Part 2.
- DPRS/IPRS installations must maintain at least 2 metres between the enclosure and the permanent wall of the nearest building or structure.
- Existing LPG manifold pipeline systems may be used for PNG supply in housing societies or residential complexes subject to relevant PNGRB guidelines.
- Previously squeezed thermoplastic pipe locations must be marked.
- The same reopened point cannot be squeezed again.
- Consecutive squeeze-off locations must be at least 1 metre apart.
- The notification does not expressly provide a separate transition period or new fee schedule.